Battery Monitoring System
WS-CUPS-DH-112
WS-CUPS-DH-112 monitors the voltage and current of each battery in the battery pack in real time, monitors the status of the battery in real time, and automatically alarms when abnormal. It can be applied to substations, switch station distribution boxes, etc. It can prevent the performance degradation of the entire battery pack caused by many battery discharge times, deep discharge, overcharging, overdischarging, battery aging, battery damage, high ambient temperature, etc., and prevent electrical fires caused by short circuits.
Main functions and characteristics

1) Flexible and convenient installation, high measurement accuracy, fast response speed, and strong system stability;

2) Able to adapt to various complex applications and intelligently determine the health level of each battery;

3) Locate faulty batteries and alarm, providing safe and reliable battery monitoring management solutions.

Technical parameter
  • Main control module
    1. Case : Dimension : 180mm x 20mm x 60mm, Protection class : IP40
    2. Power supply : External power supply : DC24V±10%, Static power consumption : ≤5W
    3. Communication : Communication port : LoRa/RS485 ; Communication protocol : Meet the "Internet of Things Micropower wireless Network Communication protocol for Power Transmission and Transformation Equipment", "Internet of Things Sensor Data Specification for Power Transmission and Transformation Equipment", and Modbus protocol ; Reporting cycle : The reporting period is configurable, the default is 15 minutes
    4. Number of connectable modules : 254
    5. Number of connectable battery packs : 6
  • Battery sensor module
    1. Case : Dimension : 65mm x 65mm x 35mm, Protection class : IP40
    2. Power supply : DC supply voltage : 0~24V, DC measurement range : 0~24V
    3. Overall voltage monitoring range : DC0~600V
    4. Temperature measurement range : -20~±100C°
    5. Maximum supply current : 26mA
    6. Isolation : >3750V
    7. Voltage measurement accuracy (25℃) : ±0.2%
    8. Internal resistance measurement range : 0.1mΩ~100mΩ
    9. Internal resistance measurement accuracy : 1.5%± 25μΩ
    10. Temperature measurement accuracy : ±1℃
  • Current detection module
    1. Case : Dimension : 65mm x 65mm x 35mm, Protection class : IP40 ;
    2. Power supply : Input power supply voltage : DC24V±10%, Monomodule power consumption : 0.5W, Isolation withstand voltage : >3750V
    3. Current measurement accuracy : 1%
    4. Current measurement range : 0~1000A
Baidu